Capacity : 5-10 KVA

Categories:

Power Electronics, HT series –Online UPS, 5-10 KVA Online UPS 1ph-1ph

  • Features
  • Technical Specification
  • Downloads
  • Wide input voltage range
  • Cold start.
  • Advanced battery management
  • Automatic battery charging oNoff mode.
  • Lighting and surge protection.
  • Automatical fan speed adjustment .
  •  Complete protection function.
  • Network/fax/modem surge protection.
  • LCD/LED display option.
  • EMURFI noise filter.
  • Smart RS232 port with monitoring software
  • PFC technology.

1PH-1PH Hykon HT Series 5KVA to 10KVA UPS

Model

Hykon HT 11 Series

Capacity

5KVA, 6KVA, 7.5KVA, 10KVA

INPUT

 

Nominal Voltage

220VAC - 230VAC

Operating Voltage Range

170 ~ 270 VAC

Operating Frequency Range

45/55 Hz

Power Factor

0.99

RECTIFIER

IGBT

OUTPUT ( INVERTER)

IGBT

Output Voltage

220 Vac ± 1% / 230 Vac ± 1%

AC Volt. Reg. (Batt. Mode)

 ± 1%

Frequency Range

50 Hz ± 1%

Crest Factor

3 : 1 (max)

Total Harmonic Distortion

<2% (linear load), <3% (non linear load)

Overload

125% : 1min; 150 % : 200ms

Transfer Time

AC mode to Batt . Mode

0 ms

Inverter to Bypass

2 ms

Power Factor

0.8

Output Isolation transformer

Inbuilt

EFFICIENCY

 

Overall

90% , 92% (optional)

Inveter

92%

BATTERY

 

Long - run Model

Battery Voltage

5KVA/120V/192V , 6KVA/192V/240V, 7.5KVA/192V, 10KVA/192/240V

Charging Curnt. (max.)

10-15 A

DISPLAY

Input Voltage, Output Voltage, Load current, Output Frequency, Battery Voltage, UPS Status

INDICATIONS

Load On Mains, Load on Battery, Battery Low, Overload, UPS Fault

ALARM

Input / Low / Fail,
Output Overload,
Over Temperature,
Battery low

ENVIRONMENT

 

Temperature

0° C    ? 40° C

Operational Humidity

0 ~ 95%

Noise Level

< 60dB ( 1m from the surface level)

COMMUNICATION

RS 232, SNMP (Optional)

PROTECTION

Advanced Electronic Protection for device safety backed up with MCB’s & fast acting
fuses, high speed pulse by pulse electronic device protection over voltage / under
voltage protection, Electronic over current trip.

image

Contact

Address

Hykon India Limited, Ikkandawarrier Road, Thrissur, Kerala,- 680 001

Phone

0487 - 2444183, 2444163

Fax

0487-2425527

Email

ho@hykonindia.com

Regional Office - Bangalore , Chennai , Hyderabad, Pune